Peak shaving: how the duration of a 100 kW peak changes battery sizing
Two companies can record the same maximum grid demand yet require different battery storage systems. Designing peak shaving requires knowing the power to be offset, how long the threshold is exceeded and how often this occurs. A numerical example shows why the maximum peak alone is not enough to choose a BESS.
November 16, 2026 · uSolar

Which part of the load must the battery cover?
Peak shaving aims to limit peak power drawn from the grid: the BESS supplies part of the power required by the site when grid demand exceeds a defined target. The production process continues to consume energy; what changes is the share supplied by the grid at that moment. The Department of Energy distinguishes this function from shifting energy use to later hours.
The analysis starts from the net load seen at the connection point, also considering any simultaneous photovoltaic production. If the planned load exceeds the chosen threshold by 100 kW, that is the power to be compensated for in the example. This does not mean that the entire company consumes 100 kW, nor that the threshold can be chosen without verifying the installation and supply.
100 kW for fifteen minutes or for two hours
Consider two illustrative cases in which the threshold is exceeded by a constant 100 kW. In the first case this lasts 15 minutes, or a quarter of an hour: the energy to be supplied is 100 × 0.25 = 25 kWh. In the second case it lasts two hours: 100 × 2 = 200 kWh are needed. The required power is identical; the energy to be supplied is eight times greater.
In the graph, the height of the two rectangles represents the 100 kW above the threshold; the width represents the time. The area is the energy to be compensated for. These are ideal cases with a constant load; not the measurements of uSolar installations: 25 and 200 kWh indicate the useful energy required at the point of compensation, not the nominal capacity of a battery to be purchased.
The data, in plain language
Same 100 kW above the threshold, different energy
The power to be compensated for is identical. If the overshoot lasts eight times longer, the ideal energy required also increases by eight times.
Short peak · 15 minutes
25 kWh
Ideal energy to be delivered, before losses and reserves.
Prolonged peak · 120 minutes
200 kWh
Ideal energy to be delivered, before losses and reserves.
Horizontal axis: minutes. Same scale 0–120 minutes. Only the power exceeding the target threshold is represented, not the total load.
Original illustrative examples in which the threshold is exceeded by a constant 100 kW: energy = power × time.
25 and 200 kWh are useful energies ideal for the point of compensation, not the recommended nominal capacities.
The calculation does not include losses, auxiliaries, reserves, operating window, temperature, or degradation. The actual system must be sized for these conditions.
From the required energy to the actually available capacity
kW describes the power that can be delivered, while kWh describes the amount of energy. The energy-to-power ratio gives a theoretical operating duration at constant power, as explained by the U.S. Energy Information Administration. To cover the example, a conversion capable of providing the required power and sufficient usable energy for the entire duration is required simultaneously.
The transition to the actual size takes into account the battery usage window, the initial charge status, losses, auxiliaries, temperature, capacity over time, and any reserves intended for other services. These checks must relate to the proposed system. Applying a single percentage margin to each project would hide differences that could affect actual performance.
The next peak may change the dimensioning
After providing energy, the BESS must recover it before the next operation, or have a sufficient reserve available from the outset. In the example, two 25 kWh events without charging possibility require a total of 50 usable kWh. The problem changes if there is a sufficiently long window of available power between the events.
Charging also enters the site’s curve: if it is powered by the grid, an excessively high command can create a new maximum draw. The control must therefore coordinate threshold, battery availability, and charge recovery. The strategy must be simulated across the entire sequence of events and verified on the functions available in the proposed system.
A lower maximum must become a verifiable benefit
The economic assessment requires the actual electricity supply terms: which cost components depend on power, over what time interval it is measured, and which peaks determine the charge. Controlling an instantaneous value and controlling an average over a time interval serve different purposes. A very brief peak should not automatically be treated as constant power demand for fifteen minutes.
The simulation must cover the relevant period, including events that the battery cannot compensate for. Recharging energy, losses and operating costs must be considered. The economic assessment does not replace electrical checks on the connection, cables, protective devices, apparent power and transients: reducing an average does not automatically make every starting surge permissible.
The data to be prepared before requesting a proposal
A useful study needs time profiles of grid imports and generation, work shifts, event frequency, electricity supply terms, an electrical diagram and planned new loads. Fast transients require measurements with adequate time resolution. The proposal should show grid imports before and after the intervention, the remaining battery charge and the time needed to recharge.
The uSolar page on industrial BESS presents the possible functions of the system. For peak shaving, the key comparison concerns the events to be managed: their magnitude, duration and frequency. This analysis allows battery storage, load scheduling and infrastructure upgrades to be assessed, individually or in combination.
The most useful questions
A 200 kWh battery always covers a peak of 100 kW for two hours?
No. At least 200 kWh of usable energy must actually be deliverable at the point concerned, together with a power output of 100 kW that can be sustained for the entire duration. The nominal capacity alone does not prove that these conditions are met.
Does peak shaving guarantee operation during a blackout?
No. Operation during a grid outage requires a dedicated configuration, compatible equipment, protective devices and an energy reserve. This is a separate capability that must be verified in the design.